E-1.1, r. 1 - Regulation respecting energy conservation in new buildings

Full text
130. The coefficient of performance for heat-operated cooling equipment, including absorption equipment, internal combustion engine driven equipment and turbine driven equipment shall be at least 0.48 if the supply is direct, by oil or gas; and at least 0.68 if it is indirect, by steam or hot water. This section does not apply to cooling systems powered by solar heat or evacuated heat that cannot be used elsewhere in the building.